6. Manufacture
6.1
Mixture—
The aggregates, cement, and water shall be
proportioned and mixed to produce a homogeneous concrete
meeting the requirements of this specification, and in accor-
dance with Specification
C94/C94M
or
C685/C685M
.
6.2
Forms—
The forms used in manufacture shall be suffi-
ciently rigid and accurate to maintain the dimensions of the
structure within the tolerances given in Section
7
. All casting
surfaces shall be of smooth nonporous material. Form releasing
agents used shall not be injurious to the concrete.
6.3
Reinforcement—
Reinforcement must be securely tied or
welded (as allowed by the design) in place to maintain position
during concrete placing operations. Where specified all chairs,
bolsters, braces, and spacers in contact with forms shall have a
corrosion-resistant surface.
6.3.1 Flexural reinforcing steel shall not exceed spacing of
12 in. (30.5 cm) center to center.
6.4
Concrete Placement—
Concrete shall be placed in the
forms at a rate such that the concrete is plastic at all times and
consolidates in all parts of the form and around all reinforce-
ment steel and embedded fixtures without segregation of
materials.
6.5
Curing—
The precast concrete sections shall be cured by
any method or combination of methods that will develop the
specified compressive strength at 28 days or less.
6.6
Concrete Quality—
The quality of the concrete shall be
in accordance with the chapter on concrete quality of ACI 318,
current edition, except for frequency of tests, which shall be
specified by the purchaser. Concrete tests shall be conducted in
accordance with Test Method
C39/C39M
.
6.6.1
Water-Cementitious Ratio—
Concrete that will be ex-
posed to freezing and thawing shall contain entrained air and
shall have water-cementitious ratios of 0.45 or less. Concrete
that will not be exposed to freezing but that is required to be
watertight shall have a water-cementitious ratio of 0.48 or less
if the concrete is exposed to fresh water. For corrosion
protection, reinforced concrete exposed to deicer salts, brack-
ish water, or seawater shall have water-cementitious ratio of
0.40 or less.
7. Tolerances
7.1
Dimensional Tolerances—
The length, width, height, or
diameter measurements of the structure when measured on the
inside surface shall not deviate from the design dimensions
more than the following:
Dimension
Tolerance
0 to 5 ft (0 to 1.5 m)
±
1
⁄
4
in. (±6 mm)
5 to 10 ft (1.5 to 3.0 m)
±
3
⁄
8
in. (±10 mm)
10 to 20 ft (3.0 to 6.1 m)
±
1
⁄
2
in. (±13 mm)
20 ft (6.1 m) and over
as agreed upon between
manufacturer and purchaser
7.2
Squareness Tolerance—
The inside of the rectangular
precast concrete component shall be square as determined by
diagonal measurements. The difference between such measure-
ments shall not exceed:
Measured Length
Allowable Difference
0 to 10 ft (0 to 3.0 m)
1
⁄
2
in. (13 mm)
10 to 20 ft (3.0 to 6.1 m)
3
⁄
4
in. (19 mm)
20 ft (6.1 m) and over
as agreed upon between
manufacturer and purchaser
7.3
Joint Surfaces—
The following joint tolerances for water
retaining structures shall apply:
7.3.1
Flexible Joint—
The inside joint seam gap between
two sections placed together before a joint sealant is applied
shall not exceed
3
⁄
8
in. (10 mm).
7.3.2
Grout Joint—
The opening to be grouted in a group
joint shall not exceed 1 in. (25 mm).
7.4
Reinforcement Location—
With reference to thickness of
wall or slab, reinforcement shall be within
6
1
⁄
4
in. (6 mm) of
the design location, but in no case shall the cover be less than
1 in. (25 mm) for water-retaining structures and
3
⁄
4
in. (19 mm)
for nonwater-retaining structures. The varations in reinforce-
ment spacing shall not be more than one tenth of the designed
bar spacing nor exceed 1
1
⁄
2
in. (38 mm). The total number of
bars shall not be less than that computed using the design
spacing.
7.5
Slab and Wall Thickness—
The slab and wall thickness
shall be uniform and shall not be less than that shown in the
design by more than 5 % or
3
⁄
8
in. (10 mm), whichever is
greater. A thickness greater than that required in the design
shall not be a cause for rejection.
8. Repairs
8.1 Repairs shall be performed by the manufacturer in a
manner to ensure that the repaired structure will conform to the
requirements of this specification.
9. Rejection
9.1 Precast concrete structures or sections of structures shall
be subject to rejection because of failure to conform to any of
the requirements contained herein.
10. Marking
10.1 The following information shall be clearly marked on
each structure or section of structure, by indentation, water-
proof paint, or other approved means:
10.1.1 Date of manufacture,
10.1.2 Name or trademark of the manufacturer, and
10.1.3 Initials or symbols to indicate the intended use of the
structure.
11. Keywords
11.1 concrete; precast; structures; wastewater; water