X2.2 Example Problem

X2.2.1 Select a Class for a concrete rectangular box to be

used as a catch basin when the invert of the base is 11 ft (3.4

m) below grade and water level is 5 ft (1.5 m) below grade.

Catch basin is in a highway.

X2.2.2 Since the catch basin is in a highway, a live load

(

LL

) from truck traffic must be considered. Refer to

Fig. X2.2

for load diagram.

X2.2.3 From

Fig. X2.2

:

h

1

5

8 ft

~

2.4 m

!

(X2.2)

h

11

5

11 ft

~

3.4 m

!

h

2

5

3 ft

~

0.91 m

!

h

22

5

6 ft

~

1.8 mm

!

P

~

1

!

5

40

3

8

1

62.4

3

3

5

507 lbf/ft

2

~

24.3 kPa

!

P

~

2

!

5

40

3

11

1

62.4

3

6

5

814 lbf/ft

2

~

38.9 kPa

!

P

5

507

1

814

2

5

660 lbf/ft

2

~

31.6 kPa

!

X2.2.4 Choose Class 700 since 700 is greater than 660. Go

to the tables with desired size to obtain information necessary

to produce the box.

X2.2.5 If P is greater than 700, the tables do not apply. An

engineer should be engaged to provide design.

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned

in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk

of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and

if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards

and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the

responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should

make your views known to the ASTM Committee on Standards, at the address shown below.

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,

United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above

address or at 610-832-9585 (phone), 610-832-9555 (fax), or

service@astm.org

(e-mail); or through the ASTM website

(www.astm.org)

. Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222

Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600;

http://www.copyright.com/

FIG. X2.2 Load Diagram

C913 − 08

6

Copyright by ASTM Int'l (all rights reserved); Mon Jun 29 17:07:04 EDT 2015

Downloaded/printed by

Jed Friesen (Predl Systems) pursuant to License Agreement. No further reproductions authorized.