![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0140.png)
steel. For butt welded splices, pull tests from representative
specimens shall develop at least 75 % of the minimum speci-
fied tensile strength of the steel.
7. Precast Concrete Manufacture
7.1
Mixture—
The aggregates shall be sized, graded,
proportioned, and mixed with such proportions of cementitious
materials and water as will produce a thoroughly-mixed
concrete of such quality that the products will conform to the
test and design requirements of this specification. All concrete
shall have a water-cementitious ratio not exceeding 0.53 by
mass. Cementitious materials shall be as specified in
4.1.2
and
shall be added to the mix in a proportion not less than 280
kg/m
3
, unless mix designs with a lower cementitious materials
content demonstrate that the quality and performance of the
product meet the requirements of this specification.
7.2
Curing—
Concrete products shall be subjected to any
one of the methods of curing prescribed in
7.2.1 – 7.2.4
or to
any other method or combination of methods approved by the
owner that will give satisfactory results.
7.2.1
Steam Curing—
Concrete products are placed in a
curing chamber, free of outside drafts, and cured in a moist
atmosphere maintained by the injection of steam for such time
and such temperatures as may be needed to enable the products
to meet the strength requirements. The curing chamber shall be
so constructed as to allow full circulation of the steam around
the entire product.
7.2.2
Water Curing—
Concrete products are water-cured by
covering with water-saturated material, or by a system of
perforated pipes, mechanical sprinklers, porous hose, or by any
other approved method that will keep the products moist during
the curing period.
7.2.3
Sealing Membrane—
A sealing membrane conforming
to the requirements of Specification
C309
is applied and shall
be left intact until the required concrete strength requirements
are met. The concrete at the time of application of the
membrane shall be within 6°C of the atmospheric temperature.
All concrete surfaces shall be kept moist prior to the applica-
tion of the membrane and shall be damp when the membrane
is applied.
7.2.4 The manufacturer is not prohibited from combining
methods prescribed in
7.2.1 – 7.2.3
provided the required
concrete compressive strength is attained.
8. Acceptance
8.1
Acceptance Procedures:
8.1.1 Unless otherwise designated by the owner at the time
of, or before, placing an order, acceptance procedures for
precast reinforced concrete manhole products shall be as
specified in the Part II section for a particular product, and shall
not be prohibited from consisting of one or more of the
following:
8.1.1.1 Acceptance of a product on the basis of tests of
materials, including concrete compressive strength and absorp-
tion.
8.1.1.2 Acceptance of a product on the basis of inspection of
the finished product, including amount and placement of
reinforcement to determine conformance with the design
prescribed under this specification, and freedom from defects.
8.2
Test Methods:
8.2.1
Concrete Compressive Strength Test:
8.2.1.1
Type of Specimen—
Compression tests for satisfying
the minimum specified concrete strength requirement shall be
made on either concrete cylinders or, at the option of the
manufacturer, on cores cut from the concrete manhole product.
8.2.1.2
Compression Testing of Cylinders—
Cylinders shall
be made in accordance with Test Methods
C497
, and shall be
tested in accordance with Test Method
C39/C39M
. For man-
hole products, an owner shall not be prohibited from requiring
concrete compressive tests on cylinder specimens numbering
in the amount of 5 % of the total order of a manhole product,
but not to exceed two cylinders for each day’s production. The
average compressive strength of all cylinders tested shall be
equal to or greater than the specified strength of the concrete.
Not more than 10 % of the cylinders tested shall fall below the
specified strength of the concrete. In no case shall any cylinder
tested fall below 80 % of the specified strength of the concrete.
8.2.1.3
Compression Testing of Cores—
Cores shall be cut
from the concrete manhole product and tested in accordance
with Test Methods
C497
, except that the requirements for
moisture conditioning shall not apply. One core shall be taken
from a manhole product selected at random from each day’s
production run of a single concrete strength. When the concrete
compressive strength of the core is equal to or greater than
80 % of the specified strength of the concrete, the concrete
strength of the production run is acceptable. If the core does
not meet the preceding concrete strength requirement, another
core from the same manhole product may be taken and tested.
8.2.1.4 If the concrete compressive strength of the recore is
equal to or greater than 80 % of the specified strength of the
concrete, the concrete strength of the production run is accept-
able. If the recore does not meet the preceding concrete
strength requirement, that manhole product shall be rejected.
Two manhole products from the remainder of the day’s
production run shall be selected at random and one core taken
from each manhole product and tested. When the average
concrete strength of the two cores is equal to or greater than
80 % of the specified strength of the concrete with no core
below 75 % of the specified strength of the concrete, the
concrete strength of the day’s production run shall be accept-
able.
8.2.1.5 If the concrete strength of the two cores does not
meet the preceding concrete strength requirement, then the
remainder of the day’s production run shall be either rejected,
or, at the option of the manufacturer, each manhole product of
the remainder of the day’s production run is not prohibited
from being cored and accepted individually.
8.2.1.6
Plugging Core Holes—
Core holes on accepted man-
hole sections shall be plugged and sealed by the manufacturer
in a manner such that the manhole products will meet all of the
requirements of this specification. Manhole sections so sealed
shall be considered as satisfactory for use.
8.2.2
Absorption Test:
8.2.2.1 The absorption of a specimen from a concrete
product, as determined in Test Methods
C497
, shall not exceed
C478M − 15
3
Copyright by ASTM Int'l (all rights reserved); Mon Jun 29 17:17:40 EDT 2015
Downloaded/printed by
Jed Friesen (Predl Systems) pursuant to License Agreement. No further reproductions authorized.